An inverter shows an error for a reason: it is protecting you, the grid or itself. Some messages mean “wait, the grid is unstable” while others mean “there is leakage in the DC wiring, do not touch.” Knowing the difference saves both money and risk. This guide covers the faults we see most often on Indian rooftops.
Why do solar inverters show error codes?
A grid-tied inverter constantly checks grid voltage, frequency, DC insulation and its own temperature, and it switches off whenever any value goes outside the limits set by grid connection standards. When it stops, it logs a fault code and the time. Every brand uses its own numbers, but the names are similar.
What do the common inverter errors mean?
| Error name (typical) | What it means | Usual cause | Owner can check? |
|---|---|---|---|
| Grid overvoltage / AC OV | Grid voltage above trip limit | High feeder voltage at noon, thin AC cable, long cable run | Note time and voltage; call installer |
| Grid undervoltage / AC UV | Grid voltage too low | Overloaded transformer, evening peak, loose neutral | Wait; report if daily |
| Grid frequency fault | Frequency outside limit | Grid disturbance, DG set running | Usually clears itself |
| No grid / grid lost | Grid supply absent | Power cut, tripped AC breaker or MCB in ACDB | Check MCB and main supply |
| Isolation fault / PV ISO low | Leakage from DC to earth | Damaged cable, water in connector, faulty panel | No, call technician |
| Residual current / GFCI / leakage current | Current leaking to earth | Moisture after rain, poor earthing | No, call technician |
| PV overvoltage | DC string voltage too high | Too many panels in a string, cold morning | No, design issue |
| Over temperature | Inverter too hot | Direct sun, no airflow, blocked fan | Clear vents, provide shade |
| Relay / self-check fault | Internal test failed | Hardware issue | Restart once; warranty claim if repeats |
| Communication / Wi-Fi offline | Monitoring not connected | Router change, weak signal | Reconfigure Wi-Fi in app |
Why does grid overvoltage happen so often in India?
This is the most common complaint we hear from April to June. Around noon, rooftop systems on the same transformer push power into the line while household load is low, so voltage rises. Indian grid rules expect the inverter to trip when voltage goes past its set limit, commonly configured in the range of about 253 V to 264 V per phase.
What helps:
- Use a thicker AC cable from inverter to ACDB and keep the run short.
- Ask your installer to check settings are as per the DISCOM’s approved grid profile. Do not ask for limits to be removed.
- If voltage at your meter is high even with solar off, write to your DISCOM about transformer tap setting.
- Run heavy loads like the water pump or washing machine during midday.
Why does my inverter stop in a power cut?
An on-grid inverter must stop when the grid fails. This is called anti-islanding, and it protects linemen working on the line. Many customers think the system is faulty when it is working as designed. If you need power during cuts, you need a hybrid inverter with a battery. Our backup guide explains the options.
What should I do when I see an isolation fault?
Treat it seriously. It means there is a leakage path between the DC wiring and earth, which can cause shock or fire. It often shows up on the first wet morning after the monsoon starts.
- Do not touch panels, DC cables or the DCDB.
- Note the code, time and weather, and take a photo of the display.
- If the fault clears by noon as things dry out, still report it. It will come back.
- Your installer will test each string with an insulation tester to find the damaged cable, connector or panel.
How do I safely restart a solar inverter?
- Switch off the AC breaker or MCB feeding the inverter (in the ACDB).
- Switch off the DC isolator on the inverter or DCDB.
- Wait at least five minutes for capacitors to discharge.
- Switch on DC first, then AC.
- Wait 1 to 5 minutes; the inverter will run its self-check and reconnect.
Restart only once or twice. If the same fault returns, restarting again will not fix it.
When is it a warranty case?
Relay faults, internal hardware errors, a dead display or a fan failure inside the warranty period are usually covered by the inverter maker. Most string inverters come with 5 to 10 years of warranty. Grid overvoltage caused by the feeder or isolation faults caused by damaged cable are not inverter defects. Our warranty claim guide explains how to file a claim and what to keep ready.
How can monitoring help?
A monitoring app or an energy management system sends an alert the moment the inverter trips, shows the voltage graph at the time and helps your installer diagnose remotely. Without monitoring, a system can sit idle for weeks before anyone notices on the bill. Read more on EMS and monitoring.
- Inverter errors fall into grid, DC-side and inverter-health groups.
- Grid overvoltage is common at noon in summer and is often a feeder or cable issue.
- “No grid” during a cut is normal for on-grid systems.
- Isolation and leakage faults are safety issues: do not touch, call a technician.
- Restart in the right order: AC off, DC off, wait, DC on, AC on.
If your inverter keeps showing the same error, send us a photo of the display and your system details on WhatsApp at +91 81819 14448, or fill in the form for a service visit or system check.
Send your electricity bill or a roof photo on WhatsApp and we will suggest the right system and price.
Frequently asked questions
Why does my solar inverter show grid overvoltage?
The inverter measures grid voltage and must disconnect if it goes above the limit set by grid rules, often around 253 to 264 V per phase depending on settings. On lightly loaded feeders with many solar systems, voltage rises in the afternoon. Your installer can check cable size and settings, and the DISCOM may need to adjust the transformer tap.
What does isolation fault or PV ISO low mean?
It means the inverter has found leakage between the DC solar wiring and earth. Common reasons are damaged cable insulation, water in a junction box or MC4 connector, or a damaged panel. It is a safety fault, so do not touch the DC wiring and call your installer.
Is it safe to restart a solar inverter myself?
Yes, if you follow the order in the manual: switch off the AC breaker, then the DC isolator, wait about five minutes, then switch on DC first and AC after. Do not open the inverter cover or the DC junction box.
Why does the inverter show no grid during power cuts?
An on-grid inverter must stop when the grid fails. This anti-islanding protection keeps linemen safe while they work on the lines. It will restart on its own a few minutes after power returns. Only hybrid inverters with a battery keep supplying backup loads in a power cut.
How do I find what my inverter error code number means?
Error numbers differ between brands. Look in the user manual or the brand's monitoring app, which usually shows the fault name along with the code. Note the exact code and time and share a photo of the display with your installer.