What is performance ratio and how is it calculated?
Performance ratio removes the effect of weather so that you can judge the plant itself. In simplified form:
- Reference yield = measured irradiation on the panel plane (kWh/m²) ÷ 1 kW/m²
- Final yield = energy exported (kWh) ÷ installed DC capacity (kWp)
- PR = final yield ÷ reference yield
Example: a 100 kWp plant receives 6.0 kWh/m² on a clear day and generates 480 kWh. Final yield is 4.8 kWh/kWp; reference yield is 6.0. PR = 4.8 ÷ 6.0 = 80%.
Without an irradiance sensor, compare specific yield (kWh/kWp) with nearby plants or with the design simulation for the same month. Read more in our guide to EMS monitoring and KPIs.
Where does the energy go? Typical losses in India
| Loss type | Typical range (Indian conditions) | Controllable? |
|---|---|---|
| Temperature | 6–12% annually; 10–15% at summer midday | Partly (ventilation, module choice) |
| Soiling (dust, bird droppings) | 2–6%; higher near industry or roads | Yes (cleaning) |
| Shading | 0–10%+ depending on site | Yes (design, trimming) |
| Module mismatch and degradation | 1–2% mismatch; ~0.4–0.7% per year degradation | Partly (quality modules) |
| DC and AC cable losses | 1–3% | Yes (design) |
| Inverter conversion | 1.5–3% | Partly (efficient inverter) |
| Inverter clipping | 0–3% depending on DC/AC ratio | Yes (design) |
| Grid unavailability and tripping | 0–5%+ on weak feeders | Partly (settings, DISCOM) |
Ranges are indicative; actual values depend on location, design and maintenance.
How do soiling and dust affect output?
India’s dry season, especially from February to June, brings heavy dust in Rajasthan, Gujarat, Delhi NCR, Uttar Pradesh and the Deccan plateau. Bird droppings are a bigger problem than they look because they create local hotspots. Diagnosis is simple: compare generation, or better PR, on the day before and after cleaning. If the jump is more than 3–4%, increase cleaning frequency.
- Clean early morning or evening with soft water and a soft brush or mop; avoid hard water that leaves scale.
- Dusty industrial sites may need weekly cleaning; others every two to four weeks.
- Monsoon rain helps, but do not assume it cleans fully; residue often stays at the lower edge of panels.
Why does heat reduce solar generation?
Crystalline modules lose about 0.3–0.4% of power for every degree Celsius above 25°C cell temperature. On a 42°C May afternoon, rooftop module cells can run at 65°C or more. To reduce temperature losses:
- Keep adequate gap below panels for airflow, particularly on metal sheet roofs.
- Prefer modules with a lower temperature coefficient.
- Install inverters in shade with ventilation; inverter thermal derating on hot afternoons is common and shows as a sagging curve after 1 pm.
How do you spot shading problems?
Shading causes a disproportionate loss because one shaded cell limits a whole string. Signs include one string consistently lower at certain times, or a sharp dip in the generation curve at the same hour each day. New water tanks, mobile towers, hoardings and growing trees are frequent culprits. Winter months bring longer shadows, so a site that was clear in April may be shaded in December. Solutions include re-stringing, separate MPPTs, optimisers or relocating affected modules.
What is inverter clipping and when is it a problem?
When the DC array is larger than the inverter’s AC rating, the inverter caps output, creating a flat top on clear days. With a DC/AC ratio of 1.1–1.25, annual clipping is usually small and worth it for the extra morning and evening yield. If the flat top lasts several hours on most days, the inverter may be undersized. See our inverter sizing guide.
What is a practical diagnosis checklist?
- Zero output: check grid availability, AC breaker, inverter display and fault code.
- Whole-plant drop: compare with irradiance; check soiling and grid tripping logs.
- One inverter lower: check temperature derating, MPPT inputs and communication.
- One string lower: inspect fuses, connectors, shading and modules; measure string Voc and Isc.
- Midday flat top: clipping or export limit setting.
- Afternoon sag: thermal derating or shade.
- Frequent trips: grid over-voltage; review inverter settings and cable sizing with your installer.
- Slow multi-year decline beyond 1% a year: commission a thermal scan or IV-curve test to detect degraded modules, PID or hotspots.
- PR of 75–85% is typical for healthy plants in India.
- Temperature and soiling are the largest routine losses.
- Compare before and after cleaning to set the right cleaning frequency.
- String-level monitoring makes shading and wiring faults easy to locate.
- Mild clipping is normal; long flat tops suggest an undersized inverter.
Is your plant underperforming? We can review your monitoring data, run on-site diagnostics and recommend corrective action. Request a performance check or see our C&I solar services.
Frequently asked questions
Why is my solar plant generating less than expected?
Common causes are dust and bird droppings on panels, high module temperatures in summer, new shading, tripped strings or breakers, inverter faults or clipping, grid outages and voltage tripping, and gradual module degradation. Monitoring data usually points to which one applies.
How much generation is lost due to dust on solar panels?
In dusty parts of India, soiling can reduce output by about 2–6% within a few weeks without rain, and more near construction sites, highways or cement and stone industries. Regular cleaning, especially in the pre-monsoon dry season, recovers most of this loss.
How does temperature affect solar panel output?
Crystalline silicon modules lose roughly 0.3–0.4% of power for every 1°C rise in cell temperature above 25°C. On Indian summer rooftops, cells can reach 60–70°C, causing losses of around 10–15% at midday.
What is inverter clipping?
Clipping happens when the panels can produce more DC power than the inverter's AC rating. The inverter caps output at its limit, so the generation curve looks flat-topped around midday. Mild clipping is a normal design trade-off; heavy clipping means the inverter is undersized.
#generation loss#performance ratio#soiling loss#solar maintenance