Why it matters
Rooftop panels and metal structures are exposed to lightning, insulation faults and static build-up. Without good earthing, a fault can make structures live, surge devices cannot work, and inverters fail after thunderstorms. Poor earthing is one of the most frequent defects found in low-cost installations.
How it works in India
| Earth pit | Connected to |
|---|---|
| Pit 1 | Module frames, structure, DC SPD |
| Pit 2 | Inverter body, AC SPD in ACDB |
| Pit 3 (dedicated) | Lightning arrester down-conductor |
- Electrodes: copper-bonded or GI rods, often with chemical earthing compound.
- Design reference: IS 3043 code of practice for earthing.
- Target resistance: low, commonly under about 5 ohms; measure with an earth tester at handover.
- Check pits yearly, ideally before the monsoon, as dry soil in summer raises resistance.
Earthing works hand in hand with the lightning arrester, ACDB and DCDB. See our maintenance guide and the EPC process.
Want a safe, properly earthed system? Get a quote.
Send your electricity bill or a roof photo on WhatsApp and we will suggest the right system and price.
Frequently asked questions
How many earth pits does a rooftop solar system need?
Common Indian practice is three: one for DC side and structure, one for AC side and inverter, and one dedicated to the lightning arrester.
What earth resistance is acceptable?
A low value, typically below about 5 ohms, is commonly specified; check your scheme or DISCOM specification.