Why it matters
Two batteries with the same nameplate kWh can deliver very different usable energy. A 10 kWh lead-acid bank kept at 50% DoD gives about 5 kWh a day; a 10 kWh LFP battery at 90% DoD gives about 9 kWh. Sizing for backup without accounting for DoD is the most common reason batteries run flat early in the evening.
How it works in India
| Chemistry | Recommended DoD | Cycles (indicative) |
|---|---|---|
| Flat-plate lead-acid | ~50% | 500–800 |
| Tubular lead-acid | 50–60% | 1,000–1,500 |
| LFP lithium | 80–90%+ | 3,000–6,000+ |
Usable energy = rated kWh × DoD × inverter efficiency. Example: to run 800 W of fans, lights and a fridge for 5 hours during load-shedding you need 4 kWh; with LFP at 90% DoD and 92% efficiency, choose about 5 kWh rated capacity. High summer temperatures also reduce life, so keep batteries in a shaded, ventilated place. A hybrid inverter lets you set the DoD limit. Size yours with the battery backup calculator and compare chemistries in lithium vs lead-acid.
Related term: BESS.
Send your electricity bill or a roof photo on WhatsApp and we will suggest the right system and price.
Frequently asked questions
What DoD should I use for a solar battery?
LFP batteries are commonly run at 80–90% DoD; tubular lead-acid batteries last longer if kept to about 50% DoD.
Does a higher DoD shorten battery life?
Yes. Deeper daily cycles reduce cycle life, so manufacturers quote cycle counts at a specific DoD, for example 6,000 cycles at 80%.